9 sdt menu, Figure 7-18. sdt configuration menu – Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual

Page 81

Advertising
background image

53MT6000 INSTRUCTION MANUAL

Database Editor 65

7.4.9 SDT Menu

There are two STATUS DISPLAY (SDT) Modules available in the 53MC5000. Each SDT module contains
eight logical status values. These logical values can be used to represent the status of discrete inputs or
outputs. The status of each of the eight inputs or outputs can have an associated point name and can also
have an associated alarm condition. The SDT module parameters may be configured by clicking on the
appropriate table entry. The window shown in

Figure 7-18

will be displayed. Any parameter can be

selected and changed.

Figure 7-18. SDT Configuration Menu

ENTRY

EXPLANATION

Module ID:

Selects the Module to be configured. Use the up or down arrow
buttons to cycle through the control module selection.

Tagname:

Tagname (title) of this STATUS DISPLAY MODULE.

Name:

User definable Point Name, 10 characters maximum.

Mode:

This parameter is used select how the Point Name is to be
displayed. A mode value of 0 uses the full 10 characters as the
point name. A mode value of 1 splits the 10 characters into two 5-
character segments. When the Point Status is 0, the first five
characters are displayed. When the status is 1, the second five
characters are displayed. Clicking on the field enables the following
selections:
No Text Toggle - One 10-character name
Text Toggle - Two 5-character names

Selecting "No Text Toggle" enters a "0" in the field while selecting
"Text Toggle" enters a "1".

Alm. Enable:

Alarm enable bit. Each status has associated with it an alarm
capability. This parameter is used to turn the alarm capability on or
off. Clicking on the field enables the following selections:
No
Yes

Selecting "No" enters a "0" in the field while selecting "Yes" enters
a "1".