SECTION 10 FUEL SUPPLY PUMP ELECTRICAL

INSTALLATION

CAUTION: HAZARD OF ELECTRICAL SHOCK


10.1 All wiring must comply with the National Electrical Code, State and Local

Ordinances, and be wired by a qualified electrician.


10.2 The electrical conductors to the fuel pump motor MUST be stranded 14 GA

minimum.


10.3 The electrical service connections for the fuel pump motor are made in the

electrical junction box on the back or side of the heater.


10.4 The pump motor MUST have a safety equipment ground from the main

electrical service, stranded 12 GA minimum.


10.5 The electrical conductors from the electrical junction box to the pump motor

must be within approved conduit.


10.6 Keep all electrical conductors and conduit away from the chimney

connector as well as any other hot surfaces. Refer to Section 18 Wiring
Diagram for color code, etc. Keep the power off until the heater is ready to
be started. Refer to Section 13 Start Up Procedure.





CAUTION: HAZARD OF ELECTRICAL SHOCK