SECTION 20 HI-320 COMBUSTION CHAMBER/HEAT

EXCHANGER CLEANING INSTRUCTIONS

CONTINUED


20.8 Replace all clean out panels. Install new gaskets each time these panels are

removed. Replace brass nuts and washers if needed. Install burner replacing
the flange gasket. Caution: Do not turn on power to the unit at this point.


20.9 Remove the chimney connector from the heater and clean all ash from the

rear of the heat exchanger (see below). Inspect chimney connector replace if
needed. When replacing chimney connector secure it the furnace with a
minimum of 3 sheet metal screws. Clean and lubricate hinge pins on the
barometric damper. Caution: When cleaning the combustion chamber/heat
exchanger protective clothing must be worn.


20.10 After replacing the chimney, and all clean out panels and cabinet doors

reconnect all power at the main breaker box. Turn the thermostat to its lowest
setting. Make sure the red light is illuminated on the preheater switch at the
rear of the burner. Wait 10 minutes for the preheaters to come up to
temperature before firing the heater.



Do not operate your furnace with clean out panels or cabinet panels
removed.

NOTE: When changing the target brick, call the Lenan Service Department

for assistance at 800-753-1601.