Is there voltage (115V) to
the black wire of the oil
primary control?


Yes

No

Is there an open circuit in the
black wire from the fan limit
control?


No

Yes


Is there voltage (115V)

Repair or tighten

to the fan/limit control

connection.

(red wire)?


Yes

No

Check wire connections in

the heaters main electrical
junction box.


Is the fan/limit control
wired properly?

Yes

No

Refer to wiring
diagram Sec. 18.

Replace fan/limit control.


Is there voltage (115V)

Check for loose orange wire

at the orange wire of the

Yes

connection at the terminal block.

oil primary control?


No



1.Replace Oil Primary Control.
2.Replace Cad Cell wires on Oil Primary Control.
3.Replace Thermostat wires on Oil Primary Control.

Questions or Comments? Call Lenan Service Department (800)753-1601.