SUPPLEMENTAL TROUBLESHOOTING

GUIDE CONTINUED

Symptom

Possible Cause

Corrective Action


7. Water in air system.

7. Clean air preheater and

drain water from system.


8. Combustion blower not

8. See flame adjustment

properly adjusted or

Section 15, page 26.

defective.

Replace blower.


9. Improper draft.

9. Check draft see page 10.

Make sure chimney is

properly installed.


10. Plugged heat exchanger,

10. Clean heater including

manifold, or chimney.

chimney.


C. Burner fires, and then

1. Contaminated fuel supply.

1. Drain and clean fuel

fails on oil primary safety.

(water/anti freeze/gear lube) supply tank.


2. Improper draft

2. See B-9.

3. Plugged heat exchanger,

3. See B-10.

manifold, or chimney.


4. Wrong air pressure.

4. See flame adjustment

page 26.


5. Wrong fuel pressure or

5. See flame adjustment

pressure fluctuating.

page 26. See fuel piping

page 12.


6. Improper combustion blower 6. See flame adjustment

setting, or blower is defective. page 26. See fuel piping

page 12.


7. Oil primary/cad cell defective. 7. Test components/adjust

Cad cell improperly adjusted. cad cell/ clean Turbulator.

Dirty flame Turbulator.


D. Burner

1. Contaminated fuel supply

1. Drain and clean supply

or dirty fuel filter.

tank. Clean filter.



Page 46