Lanair HI320 User Manual

Page 58

Advertising
background image

1. Jump the cad cell circuit. See Sec. 17,17.2.
2. Disable transformer, Caution Hazard of Electrical Shock. Disconnect neutral wire from terminal

and oil primary wire in burner electrical junction box.

3. Adjust burner air/filter regulator to 11-12 PSI.
4. Disconnect air line at air preheater.
5. Start burner, does the air valve open and allow air to exit air line
to preheater?

Yes

No

Is there air pressure

Is there voltage (115V)

to the air valve?

to the air valve?


Yes

No


Is the air valve plugged?

Is there pressure to

the burner air/filter regulator?

Yes

No

Yes

Check burner air/filter regulator for

Clean air valve.

Replace air Valve.

proper operation

.

No

Yes

Check primary air
regulator for
proper operation.

Does Air operated Fuel
Valve function properly?
Refer to Sec. 17, 17.9.

No

Is the 5/8" OD O-Ring
at diaphragm leaking?

No

Yes


Yes

Is the 1/4" OD O-Ring

Replace O-Ring

between adaptor. and air
preheater leaking?

No

Yes


Replace O-Ring