SECTION 13 START UP PROCEDURE

13.1

Make sure the main electrical service for the heater is turned off, and
locked out.


13.2

Fill the oil supply tank with an approved fuel to a level that is above the
pick-up tube check valve.


13.3

Check for proper draft in the chimney. The draft must read -.02 W.C. cold.


13.4

Make sure there is air pressure at the heaters air filter/regulator, set it at
12 PSI. Set the primary regulator on the air supply line to 30 PSI.


13.5

Set the fan/limit control slide switch to automatic.


13.6

Check the combustion air adjustment baffle for proper setting. Refer to
Section 15 Flame adjustment.


13.7

Set the room thermostat below room temperature (OFF).


13.8

Push the reset button on the oil primary control for 3 seconds.


13.9

Turn the main electrical service ON.


13.10 Flip the lighted rocker switch for preheating on the burner electrical box to

the ON position (Preheater OFF the light is off, Preheater ON the light is
on.).


13.11 Prime the fuel supply pump. Refer to Section 14, Priming the Fuel Supply

Pump.


13.12 If using waste10W-50W oil or automatic transmission fluid for fuel, flip

the preheater rocker switch on (light ON, and wait 5-7 minutes for the
preheater assembly to reach operating temperature. Leave the preheater
switch OFF if using No. 1 or No. 2 fuel oil.).


13.13 Turn the room thermostat up above the room temperature. The burner

will now fire, check the sight glass on the rear of the burner also inspect
the flame through the inspection port. (See page 26AA for proper flame
settings.).


Page 22