Supplemental trouble shooting guide continued – Lanair HI320 User Manual

Page 62

Advertising
background image

Supplemental Trouble Shooting Guide Continued

Symptom

Possible Cause

Corrective Action


A. Burner will not start.

1. Main electrical power

1. Reset Breaker.

circuit breaker tripped.


2. Service disconnect

2. Turn switch on or

switch off or fuse blown.

replace fuse.


3. Thermostat turned down/

3. Turn thermostat up,

improperly installed/

check wires/test

defective.

components/replace.


4. Oil primary safety

4. Reset/test components,

tripped/defective.

replace if needed.

5. Too much light showing

5. Eliminate light to cad

on cad cell/defective.

cell. Test component.


6. Fan/Limit control reached

6. Check fan/limit control

. high/limit, or is defective settings (See page

13B) or test components.


B. Burner attempts to

1. Low oil in supply tank or

1. Fill tank, or drain and

fire, but does not

contaminated fuel.

clean tank.

establish a flame.

2. Plugged or worn nozzle.

2. Clean or replace.


3. Fuel pressure gauge

3. See section 7, Page 12.

fluctuating/pumping system.


4. Preheater switch is turned off 4. Turn switch on or test

off or defective, or defective switch and cartridge

cartridge heater.

cartridge heater.


5. Transformer/electrodes not

5. Test transformer/look

sparking.

for shorts & repair.

Replace electrodes/

transformer.


6. No air pressure/defective

6. Turn compressor on/test

regulator/defective solenoid. regulator/solenoid.

Replace defective
components.

Page 45