Lanair HI320 User Manual

Page 60

Advertising
background image

Section 17 Trouble Shooting Flow Chart #4

"Caution: Hazard Of Electrical Shock"



Symptoms:

1. Preheater cold with preheater switch on?
2. Burner attempts to fire but fails?
3. Unable to establish a flame?
4. Oil Primary locks out?
5. Preheater switch on, is the preheater switch light on?


No



Yes

Is there voltage (115V) to the preheater switch?


No


Replace preheater switch.

Is there voltage (115V) going to the heating

elements from the snap switch?

Yes

No

Replace snap switch, or repair loose wire

connections.



Does the 1/4" Dia. heating element have
Internal resistance of 112 OHMS ±10,
at room temperature?

Yes

No


Does the 3/8" Dia. heating

Replace 1/4" heating element.

element have internal resistance of
37 OHMS ±10% at room temperature.


Yes

No


Check for loose wire

Replace 3/8" heating element.

connections and repair.


Page 43

Advertising