Section 17 Trouble Shooting Flow Chart #3

Caution: Hazard of Electrical Shock

Symptoms:

1. Burner attempts to fire.
2. Poor flame.
3. No flame established.
4. Correct fuel output (see sec. 17, 17.1).
5. Oil Primary may lock out.
Note: Disable air operated fuel valve. Adjust burner air filter regulator to -0- PSI.

Look in inspection port at rear of burner.
Wear eye and face protection. Start
burner, do electrodes have spark? No

Are electrodes grounding out?


Yes

No


Remove electrodes

Is there voltage

clean or replace

(115V) to the ignition

see sec. 16.5.

transformer?



Yes

Yes

No


Replace the ignition

Check for loose

transformer.

wire connections.




Is the combustion air blower working?

No

Is there voltage (115V) to the
combustion air blower motor?


Yes

Yes

No

Replace combustion

Check for loose

air blower motor.

wire connections.