22] pio inch distance (parameter no.25) – IAI America MSEP User Manual

Page 220

Advertising
background image

Chapter 5 I/O Parameter

212

[21] Zone 1+, Zone 1- (Parameter No.21, No.22)

Zone 2+, Zone 2- (Parameter No.23, No.24)



No.

Name

Symbol

Unit

Input Range

Default factory

setting

21 Zone 1+

ZONM

mm

[deg] -9999.99 to 9999.99

Actual stroke on

+ side

22 Zone 1-

ZONL1

mm

[deg] -9999.99 to 9999.99

Actual stroke on

- side

23 Zone 2+

ZNM2

mm

[deg] -9999.99 to 9999.99

Actual stroke on

+ side

24 Zone 2-

ZNL2

mm

[deg] -9999.99 to 9999.99

Actual stroke on

- side

Set the area where thzone signals (ZONE1 and ZONE2) turn ON.

The minimum setting unit is 0.01mm [deg].

If a specific value is set to both zone setting + and zone setting -, the zone signal is not

output.

A setting sample is shown below.

[Example of linear axis]

0mm

30mm

70mm

ON

ON

ON

100mm

Current Position

Zone signal output

Zone signal output

Set Value

Zone setting + : 70mm

Zone setting - : 30mm

Set Value

Zone setting + : 30mm

Zone setting - : 70mm

Caution: The signal cannot be output unless the range of the zone detection is set to a value

greater than that of the minimum resolution (actuator lead length/encoder resolution).

[22] PIO inch distance (Parameter No.25)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

25 PIO inch distance

IOID

mm

0.01 to 1.00

0.1

The inching distance to the inching input command from PLC is set.

(Note) The maximum allowable value is 1 mm.