Chapter 5 Handling Errors

160

Phenomenon

Possible cause

No home return operation is performed.

Cause: [1] Wrong settings of output ports.

[2] Disconnection of home return command

signal.

[3] The operation mode of the RC controller

prohibits launching PIO.

Action: [1] Check if the setting of I/O parameters

(extension motion control board control

output port head No.) of X-SEL is correct.

[2] Check disconnection of home return

command signal of a control I/O cable and

poor contact of connectors.

[3] Check if the operation mode of the RC

controller prohibits launching PIO.

Moreover, check if the MANU mode is set.

* Although X-SEL performs timeout check, it takes 150

seconds until error No. 453 “Extension motion control

board axis home return completion timeout error”

(parameter default value) taking long stroke into

consideration.

The home return command of X-SEL is not completed

even if home return operation of RC axis is completed.

Cause: [1] Wrong settings of input ports.

[2] Disconnection of home return command

signal.

Action: [1] Check if the setting of I/O parameters

(extension motion control board control

input port head No.) of X-SEL is correct.

[2] Check disconnection of home return

command signal of a control I/O cable and

poor contact of connectors.

* Although X-SEL performs timeout check, it takes 150

seconds until error No. 453 “Extension motion control

board axis home return completion timeout error”

(parameter default value) taking long stroke into

consideration.

Error No. 47D “Pulse train driver home return

completion signal OFF error” occurs.

Cause: Home return complete signal from the RC

controller was disconnected after completion of

home return. The home return complete signal

may be disconnected.

Action: Check disconnection and/or connection status

of home return complete status of a control I/O

cable.