General specifications

Operating conditions

Operating temperature
(Surrounding air
temperature)

-10 to +55℃ (no freezing)

Relative operating humidity

10 to 95% (non-condensing)

Storage temperature

-40 to +70℃ (no freezing)

Relative storage humidity

10 to 95% (non-condensing)

Pollution degree

2(IEC/EN 60664-1)

Degree of protection

IP20(IEC/EN 60529)

Corrosion immunity

Atmosphere be free from corrosive gas

Operation: 0 to 2,000m (0 to 6,565 feet)

Altitude

Transportation: 0 to 3,000m (0 to 9,840 feet)

Vibration resistance

Vibration (IEC/EN 61131-2):

5 to 8.4 Hz amplitude 3.5 mm,
8.4 to 150 Hz acceleration 9.8 m/s

2

(1G),

2 hours per each of XYZ axes

Bump (IEC/EN 61496-1):
Acceleration 98 m/s

2

(10G), 16ms duration, 1000 times per

each of XYZ axes

Shock resistance

147 m/s

2

(15G), 11 ms duration, 3 times per each of XYZ axes

IEC/EN 61131-2)

Connector durability

50 times maximum

Operation strength of
configuration switches

100 operations maximum (per 1 switch)

Operation strength of
enter button

1000 operations maximum

Enclosure material

modified-Poly Phenylene Ether (m-PPE)

Weight Approximately

330g

Electrical conditions

Rated voltage

24V DC

Allowable voltage range

20.4V DC to 28.8V DC

Maximum power
consumption

48W (at 24V DC, all inputs and outputs are ON,

includes output loads)

Allowable momentary
power interruption

10ms minimum (at rated voltage DC)

ON to OFF: 40 ms maximum

Note1

: 100ms maximum

Note2

Reaction time

OFF to ON: 100 ms maximum

Note3

Start-up time

Note4

6s

maximum

Between live part and FE terminal: 500VAC, 1 minute

Dielectric strength

Between enclosure and FE terminal: 500VAC, 1 minute

Between live part and FE terminal: 10MΩ minimum

at 500V DC megger)

Insulation resistance

Between enclosure and FE terminal: 10MΩ minimum

at 500V DC megger)

DC power terminals: 1.0 kV, 50 ns to 1 µs

Noise immunity
(Noise simulator)

I/O terminals: 2.0 kV, 50 ns to 1 µs (with coupling adapter)

Inrush current

25A maximum

Grounding

Type D grounding (Type 3 grounding)

Reverse polarity: No operation, no damage

Affect of improper power
supply connection

Improper voltage: Permanent damage may occur