Wiring method – IDEC FS1A Controller User Manual

Page 31

Advertising
background image

3-6

Wiring method

SafetyOne has to two kinds of connectors = spring clamp = (optional) and crimp.

Note1


Note1. For detailed information of Crimp connector, consult Tyco Electronics AMP.

●Applicable connectors and mounting to SafetyOne
Applicable connectors

Type

No. of pole

Part No.

Remarks

FS9Z-CN01

IDEC (optional)

30

2-1871940-5

Tyco Electronics AMP

FS9Z-CN02

IDEC (optional)

Spring clamp

22

2-1871940-1

Tyco Electronics AMP

30

2-1871946-5

Tyco Electronics AMP

Crimp

22

2-1871946-1

Tyco Electronics AMP









Fig. 3.6 Spring clamp connector (FS9Z-CN0*) Fig. 3.7 Clamp connector

When mounting a connector to the SafetyOne, be sure to insert the connector straight and
completely in until you hear a click or feel it click into position. To remove the connector, press
down on the lock completely, and then pull out the connector. If pressing down on the lock is
incomplete damage to the connector and wire may occur.

● Applicable wire and ferrule sizes for Spring clamp connector
AWG#18-24 (UL1007 recommended) Stripped length: 7.0±0.3mm
When using ferrules, specification are shown below.
Long size: 1.02mm (min.) - 1.21mm (max.) (”a” in the figure below)
Short size: 0.95mm (min.) - 1.21mm (max.) (”b” in the figure below)
Applicable wire: AWG#24 (UL1007 recommended)



Fig3.8 Applicable Ferrule

Locking parts

Tool insertion slot

Wire insertion slot

a

b

Wire

Terminal

Ferrule