Control start, Description of operation – IDEC FS1A Controller User Manual

Page 140

Advertising
background image

5-99

Control start

This function confirms operation of the connected start input device. As shown in Fig.5-26, this
function is comprised of a functional input (I

n

) and a functional output (O

n

).

The start input (I

n

) ON operation is monitored to determine whether it is performed within the

designated control time (0.1 s to 5 s).

Fig. 5-26 Control start circuit

Description of operation

The operation timing is described in Fig. 5-27.

If the input turns ON within the designated control time (0.1 s to 5 s), the output turns ON until

the connected self-holding function or another trigger input turns ON. (The function output
turns OFF after the other trigger input turns ON.)

If the input does not turn ON within the designated control time (0.1 s to 5 s) (If the function

input turns on before 0.1 s or after 5 s), the output does not turn ON.

I

n

O

n

Control time
:0.1s~5s

0.1s

5s

0.1s

5s

Control time
:0.1s~5s

ON

OFF

ON

OFF

Fig. 5-27 Operation timing of the control start function





I

n

O

Control

Start

Control