Timing chart (logic 4) – IDEC FS1A Controller User Manual

Page 79

Advertising
background image

5-38

Timing chart (Logic 4)

Safety input : X0

Manual start input
: X16

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

Muting lamp
output : Y17

Power ON

Off delay time

Muting input : X2

(X4, X5, X10...X13 are ON and X6, X7 are OFF in this chart.)

RUN monitor :
Y16

(Note 1)

Note 1: When the safety inputs were turned OFF before the muting inputs were turned ON, the muting functions are not effective

and the safety outputs are not turned ON.

Muting start

Muting end

Muting start

Muting end

Note 2: When the muting inputs are turned ON while the safety inputs are ON, the muting functions are effective and the safety
outputs are turned ON upon input of the start input.

1.Example of using the manual start input (X16)

Min. 0.1s

Max. 6s

Safety output

ON

Safety input : X1

(Note 3)

Note 3: When the input time difference at the dual channel solid state inputs (X0-X1, X4-X5) is greater than 0.1s

input monitor error is detected.
When the input time difference at the dual channel direct opening inputs

(X10-X11, X12-X13) is greater than 0.5s

input monitor error is detected.
Refer to the following "Logic functions" for details.

(Note 3)

Max. 0.1s

Safety output

ON

( Note 2)

(Note 3)

Min. 0.1s

Max. 0.1s

Initialization

Muting input : X3

(Note 1)

(Note 4)

(Note 4 )

Note 4: When the input time difference at the muting inputs (X2-X3, X6-X7) is greater than 3s input monitor error is detected.
Refer to the following "Logic functions" for details.