5-6

●State monitor outputs: Y14 to Y16

Y14 to Y16 are monitor outputs for the internal status of the SafetyOne.
Y14 turns ON when in the Initial or Stop state.
Y15 turns ON in the Initial, Protection or Configuration state.
Y16 turns ON when in the Run state.
Refer to “Chapter 4 BASIC OPERATION”, or “Chapter 6 TROUBLESHOOTING”, for details of the
each state.

Warning

The monitor outputs are not safety outputs. Do not use these to construct of a safety system.

●Solenoid outputs: Y17 and Y20

Y17 and Y20 are outputs for solenoid control that are used for a safety switch with a lock.
In the Run state, when the safety outputs are OFF and 1 or more safety inputs are OFF, the
solenoid outputs are turned ON. When all safety inputs are ON, the solenoid outputs are turned
OFF, although the start input is not activated.

Warning

Solenoid outputs are not safety outputs. Do not use these to construct of a safety system.

Caution

Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.