Energy Savings Mode / Optional Accel/Decel

Energy Saving Mode – This function allows the inverter to deliver the minimum power
necessary to maintain speed at any given frequency. This works best when driving
variable torque characteristic loads such as fans and pumps. Parameter A085=01
enables this function and A086 controls the degrees of its effect. A setting of 0.0 yields
slow response but high accuracy, while a setting of 100 will yield a fast response with
lower accuracy.

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Operation mode selection

A085

RUN MODE

NOR

Three option codes:
00

}Normal operation

01

}Energy-saver operation

U

00

00



Energy saving mode tuning

A086

ECO Adj

0050.0%

Range is 0.0 to 100 %.

U

50.0

50.0

%

The acceleration time is controlled so that the output current below the level set by the
Overload Restriction Function if enabled (Parameters b021, b022, and b023). If
Overload Restriction is not enabled, then the current limit used is 150% of the inverter’s
rated output current.

The deceleration time is controlled so that the output current is maintained below 150%
of the inverter’s rated current,

and

the DC bus voltage is maintained below the OV Trip

level (400V or 800V).

NOTE: If the load exceeds the rating of the inverter, the acceleration time may be increased.

NOTE: If using a motor with a capacity that is one size smaller than the inverter rating,
enable the Overload Restriction function (b021) and set the Overload Restriction Level
(b022) to 1.5 times the motor nameplate current.

NOTE: Be aware that the acceleration and deceleration times will vary, depending on the
actual load conditions during each individual operation of the inverter.