Analog Input Current/Voltage Select

The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI]
input terminals for external frequency control. When intelligent input [AT] is ON, you
can set the output frequency by applying a current input signal at [OI]-[L]. When the
[AT] input is OFF, you can apply a voltage input signal at [O]-[L] to set the output
frequency. Note that you must also set parameter A001 = 01 to enable the analog
terminal set for controlling the inverter frequency.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

16

AT

Analog Input
Voltage/Current
Select

OFF

See the table down below

Valid for inputs:

C001~C005

Required settings

A001 = 01

Notes:
x If the [AT] option is not assigned to any

intelligent input terminal, then inverter
recognizes [AT] = OFF in following table.

Combination of A005 setting and [AT] input
for analog input activation.

x Be sure to set the frequency source setting

A001=01 to select the analog input terminals.

Example (default input configuration shown
for –FU models; –FE models require input
configuration—see

page 3–49

):

See I/O specs on

page 4–6.

NOTE: You cannot use both the [O] and [OI] inputs at the same time on the X200
inverter.

5

4

3

2

1

L PCS P24

AT

AM H

O OI

L

Å

+ -

4-20 mA

0-10 V

4

22

Operations and

Monitori

ng

A005

[AT] Input

Analog Input Configuration

ON

Keypad Pot

02

OFF

[O]

ON

Keypad Pot

03

OFF

[OI]

04

(ignored)

[O]

05

(ignored)

[OI]

4

−22

Operations and

Monitoring