Restoring Factory Default Settings

You can restore all inverter parameters to the original factory (default) settings for the
intended country of use. After initializing the inverter, use the powerup test in Chapter
2 to get the motor running again. To initialize the inverter, follow the steps below.

No.

Action

Display

Func./Parameter

1

Use the

,

, and

keys to

navigate to the “B” Group.

b---

“B” Group selected

2

Press the

key.

b001

First “B” parameter selected.

3

Press and hold the

key until

Æ

b085

Country code for initialization
selected

4

Press the

key.

02

00=Japan, 01=Europe
02=USA

5

Confirm the country code is correct. Do not change it unless you are absolutely sure
the power input voltage range and frequency matches the country code setting.

To change the country code, press

or

to set,

to store.

6

Press the

key.

b085

Country code for initialization
selected

7

Press the

key.

b084

Initialization function selected

8

Press the

key.

00

00=initialization disabled, clear
trip history only

9

Press the

key.

01

01=initialization enabled

10

Press the

key.

b084

Initialization now enable to
restore all defaults

11

Press and hold the

,

and

keys. Do not release yet.

b084

EU

USA

JP

d001

First part of special key sequence

12

When your country code appears in
the display, release all the keys.

Default parameter country code
shown during initialization
process (left-most char displays
alternating pattern)

13

Initialization is complete

Function code for output
frequency monitor shown

NOTE:

Initialization cannot be performed with a remote operator panel. Disconnect the dovice