The following table lists the holding registers for the “A” Group Standard Functions.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

A001

Frequency source
setting

R/W Five options; select codes:

00...Keypad potentiometer
01...Control terminal
02...Function F001 setting
03...ModBus network input
10...Calculate function output

1019h

0 to 3, 10



A002

Run command source
setting

R/W Three options; select codes:

01...Control terminal
02...Run key on keypad, or
digital operator
03...ModBus network input

101Ah

1, 2, 3



A003

Base frequency setting

R/W Settable from 30 Hz to the

maximum frequency

101Bh 30 to max.

freq.

1 Hz

A203

Base frequency setting,
2nd motor

R/W Settable from 30 Hz to the 2nd

maximum frequency

150Ch 30 to max.

freq.2

1 Hz

A004

Maximum frequency
setting

R/W Settable from the base frequency

up to 400 Hz

101Ch

30 to 400

1 Hz

A204

Maximum frequency
setting, 2nd motor

R/W Settable from the 2nd base

frequency up to 400 Hz

150Dh

30 to 400

1 Hz

A005

[AT] selection

R/W Five options, select codes:

00... Select between [O] and [OI]

at [AT]

02... Select between [O] and
keypad potentiometer
03... Select between [OI] and
keypad potentiometer
04... Only [O] input active
05... Only [OI] input active

101Dh

0, 2, 3,

4, 5



A011

O–L input active range
start frequency

R/W The output frequency

corresponding to the analog
input range starting point,
Range is 0.0 to 400.0

1020h

0 to 4000

0.1 Hz

A012

O–L input active range
end frequency

R/W The output frequency

corresponding to the analog
input range ending point, range
is 0.0 to 400.0

1022h

0 to 4000

0.1 Hz

A013

O–L input active range
start voltage

R/W The starting point (offset) for the

active analog input range, range
is 0. to 100

1023h

0 to 100

1 %

A014

O–L input active range
end voltage

R/W The ending point (offset) for the

active analog input range, range
is 0. to 100.

1024h

0 to 100

1 %

A015

O–L input start
frequency enable

R/W Two options; select codes:

00...Use offset (A011 value)
01...Use 0 Hz

1025h

0, 1



A016

External frequency
filter time constant

R/W Range n = 1 to 16, where n =

number of samples for average.
Set 17 to use 16-samples for avg.,
plus deadband +0.1/-0.2Hz

1026h

1 to 17

1 sample

B

25

Appe

ndix B

B

−25

Appendix B