The two diagrams below show input wiring circuits using an external supply. If using
the “Sinking Inputs, External Supply” in below wiring diagram, be sure to remove the
short bar, and use a diode (*) with the external supply. This will prevent a power supply
contention in case the short bar is accidentally placed in the incorrect position. For the
“Sourcing Inputs, External Supply”, please connect the short bar as drawn in the
diagram below.

Sinking Inputs, External Supply

Short bar = Removed

GND

5

1

Field device

Open collector outputs,
NPN transistors

X200

P24

1

5

24V

PCS

Input
circuits

+

-

Logic GND

Input common

Input switches

L

24V

+

-

+

-

24V

*

*

* Note: If the external power supply to GND is (optionally)
connected to [L], then install the above diode.

Sourcing Inputs, External Supply

Short bar = [PCS] – [L]

5

1

Field device

X200

P24

1

5

24V

PCS

Input
circuits

+

-

Input common

Input switches

L

GND

PNP transistor
sourcing outputs

24V

+

-

24V

+

-

Short bar