Software Lock

When the terminal [SFT] is turned ON, the data of all the parameters and functions
(except the output frequency, depending on the setting of B031) is locked (prohibited
from editing). When the data is locked, the keypad keys cannot edit inverter parameters.
To edit parameters again, turn OFF the [SFT] terminal input.

Use parameter B031 to select whether the output frequency is excluded from the lock
state or is locked as well.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

The keypad and remote programming devices are
prevented from changing parameters

15

SFT

Software Lock

OFF

The parameters may be edited and stored

Valid for inputs:

C001~C005

Required settings

B031 (excluded from lock)

Notes:
x When the [SFT] terminal is turned ON, only the

output frequency can be changed.

x Software lock can include the output frequency

by setting B031.

x Software lock by the operator is also possible

without the [SFT] terminal being used (B031).

Example (requires input configuration—
see

page 3–49

):

See I/O specs on

page 4–6.