Set the Motor Base Frequency – The motor is designed to operate at a specific AC
frequency. Most commercial motors are designed for 50/60 Hz operation. First, check
the motor specifications. Then follow the steps below to verify the setting or correct it
for your motor. DO NOT set it greater than 50/60 Hz unless the motor manufacturer
specifically approves operation at the higher frequency.

Action

Display

Func./Parameter

(Starting point)

A002

Run command source setting

Press the key once.

A003

Base frequency setting

Press the key.

60.0

or

50.0

Default value for the base frequency.
US = 60 Hz, Europe = 50 Hz

Press the or key as needed.

60.0

Set to your motor specs (your display
may be different)

Press the key.

A003

Store parameter, returns to “A”
Group list

CAUTION: If you operate a motor at a frequency higher than the inverter standard
default setting (50Hz/60Hz), be sure to check the motor and machine specifications with
the respective manufacturer. Only operate the motor at elevated frequencies after
getting their approval. Otherwise, there is the danger of equipment damage.

Set the AVR Voltage Setting – The inverter has an Automatic Voltage Regulation (AVR)
function. It adjusts the output voltage to match the motor’s nameplate voltage rating.
The AVR smoothes out fluctuation in the input power source, but note that it does not
boost the voltage in the event of a brown-out. Use the AVR setting (A082) that most
closely matches the one for your motor.

x

200V class: 200 / 215 / 220 / 230 / 240 VAC

x

400V class: 380 / 400 / 415 / 440 / 460 / 480 VAC

TIP: If you need to scroll through a function or parameter list, press and hold the or
key to auto-increment through the list.

To set the motor voltage, follow the steps on the following page.