XLT Hitachi X200 User Manual

Page 79

Advertising
background image

Action

Display

Func./Parameter

(Starting point)

A003

Base frequency setting

Press the key and hold until

Æ

A082

AVR voltage select

Press the key.

230

or

400

Default value for AVR voltage:
200V class = 230VAC
400V class = 400VAC (HFE)

= 460VAC (HFU)

Press the or key as needed.

215

Set to your motor specs (your display
may be different)

Press the key.

A082

Store parameter, returns to “A”
Group list

Set the Motor Current – The inverter has thermal overload protection that is designed
to protect the inverter and motor from overheating due to an excessive load. The
inverter’s uses the motor’s current rating to calculate the time-based heating effect.
This protection depends on using correct current rating for your motor. The level of
electronic thermal setting, parameter B012, is adjustable from 20% to 120% of the
inverter’s rated current. A proper configuration will also help prevent unnecessary
inverter trip events.

Read the motor’s current rating on its manufacturer’s nameplate. Then follow the steps
below to configure the inverter’s overload protection setting.

Action

Display

Func./Parameter

(Starting point)

A082

AVR voltage select

Press the key.

A- - -

“A” Group selected

Press the key.

b- - -

“B” Group selected

Press the key.

b001

First “B” Group parameter selected

Press the key and hold until

Æ

b012

Level of electronic thermal setting

Press the key.

1.60

Default value will be 100% of
inverter rated current

Press the or key as needed.

1.80

Set to your motor specs (your display
may be different)

Press the key.

b012

Store parameter, returns to “B”
Group list

FUNC

STR

1

1

2

FUNC

1

FUNC

1

1

2

FUNC

STR

2

32

Inverter Mounting

and i

n

st

all

ation

2

−32

Inverter Mountingand

installation

Advertising