Network protocol reference, B 6 – XLT Hitachi X200 User Manual

Page 249

Advertising
background image

Network Protocol Reference

Transmission procedure

The transmission between the external control equipment and the inverter takes the
procedure below.

x Query - A frame sent from the external control equipment to the inverter

x Response - A frame returned from inverter to the external control equipment

The inverter returns the response only after the inverter receives a query from the
external control equipment and does not output the response positively. Each frame is
formatted (with commands) as follows:

Frame Format

Header (silent interval)
Slave address
Function code
Data
Error check
Trailer (silent interval)

Message Configuration: Query

Slave address:

x This is a number of 1 to 32 assigned to each inverter (slave). (Only the inverter

having the address given as a slave address in the query can receive the query.)

x When slave address “0” is specified, the query can be addressed to all inverters

simultaneously. (Broadcasting)

x In broadcasting, you cannot call and loop back data.

B

6

Appe

ndix B

B

−6

Appendix B