Control Logic Signal Specifications

The control logic connectors are located just
behind the front housing cover. The relay
contacts are just to the left of the logic connectors.
Connector labeling is shown below.

Terminal Name

Description

Ratings

[P24]

+24V for logic inputs

24VDC, 30mA. (do not short to terminal L)

[PCS]

Intelligent input common

Factory set: Source type for –FE and –HE
models (connecting [P24] to [1]~[5] turns
each input ON). To change to sink type,
remove the short wire between [PCS] and
[L], and connect it between [P24] and [L]. In
this case, connecting [L] to [1]~[5] makes
each input ON.

[1], [2], [3], [4], [5]

Discrete logic inputs

27VDC max. (use PCS or an external
supply referenced to terminal L)

[L] (right) *1

GND for logic inputs

Sum of input [1]~[5] currents (return)

[11]

Discrete logic output

50mA max. ON state current,
27 VDC max. OFF state voltage

[CM2]

GND for logic output

100 mA: [11] current return

[AM]

Analog voltage output

0~10VDC 1mA maximum

[L] (left) *2

GND for analog signals

Sum of [OI], [O], and [H] currents (return)

[OI]

Analog input, current

4 to 19.6 mA range, 20 mA nominal,
input impedance 250

:

[O]

Analog input, voltage

0 to 9.8 VDC range, 10 VDC nominal,
input impedance 10 k

:

[H]

+10V analog reference

10VDC nominal, 10mA max.

[AL0]

Relay common contact

[AL1] *3

Relay contact, normally open

[AL2] *3

Relay contact, normally closed

250VAC,

2.5A (R load) max.

250VAC,

0.2A (I load, P.F.=0.4) max.

100VAC,

10mA min.

30VDC,

3.0A (R load) max.

30VDC,

0.7A (I load, P.F.=0.4) max.

5VDC, 100mA min.

Note 1:

The two terminals [L] are electrically connected together inside the inverter.

Note 2:

We recommend using [L] logic GND (to the right) for logic input circuits and
[L] analog GND (to the left) for analog I/O circuits.

Note 3:

Default relay N.O./N.C. configuration is reversed. See

page 4-35

.

4

6

Operations and

Monitori

ng

AL2 AL1 AL0

Relay
contacts

AM H

O OI

L

5

4

3

2

1

L PCS P24 CM2 11

Analog
output

Analog
inputs

Logic inputs

Logic
output

Short bar : default position (Source logic)