XLT Hitachi X200 User Manual

Page 195

Advertising
background image

Analog Input Disconnect Detect

This feature is useful when the inverter receives a speed reference from an external
device. Upon input signal loss at either the [O] or [OI] terminal, the inverter normally
just decelerates the motor to a stop. However, the inverter can use the intelligent output
terminal [Dc] to signal other devices that a signal loss has occurred.

Voltage signal loss at [O] terminal - Parameter B082 is the Start Frequency Adjustment.
It sets the beginning (minimum) output frequency when the speed reference source is
greater than zero. If the analog input at terminal [O] is less than the Start Frequency,
the inverter turns ON the [Dc] output to indicate a signal loss condition.

Current signal loss at [OI] terminal - The [OI] terminal accepts a 4mA to 20mA signal,
with 4mA representing the beginning of the input range. If the input current falls below
4mA, the inverter applies a threshold to detect signal loss.

Note that a signal loss is not an inverter trip event. When the analog input value is again above
the B082 value, the [Dc] output turns OFF. There is no error condition to clear.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

when the [O] input value < B082 Start Frequency
Adjustment (signal loss detected), or when the [OI
input current is less than 4mA

06

Dc

Analog Input
Disconnect Detect

OFF

when no signal loss is detected

Valid for inputs:

11, AL0 – AL2

Required settings

A001=01, B082

Notes:

x The [Dc] output can indicate an analog signal

disconnect when the inverter is in Stop Mode, as
well as Run Mode.

x The example circuit for terminal [11] drives a

relay coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the
coil from damaging the inverter’s output
transistor.

Example for terminal [11] (default output
configuration shown – see

page 3-54

):

Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see

page 4-35 and 3-54

):

See I/O specs on

page 4-6

4

46

Operations and

Monitori

ng

RY

Inverter output
terminal circuit

CM2

11

Dc

AL1

Power
supply

Load

AL0

AL2

Inverter logic
circuit board

Dc

4

−46

Operations and

Monitoring

Advertising