Trip event and history monitoring – XLT Hitachi X200 User Manual

Page 90

Advertising
background image

“D” Function

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

Units

Scaled output frequency
monitor

D007

F-Cnv

00000.00

Displays the output frequency
scaled by the constant in B086.
Decimal point indicates range:
XX.XX

0.00 to 99.99

XXX.X

100.0 to 999.9

XXXX.

1000. to 9999.

XXXX

1000 to 9999
(x10=10000 to 99999)



Hz times

constant

Output voltage monitor

D013

Vout

00000V

Voltage of output to motor,
Range is 0.0 to 600.0V



V

Cumulative operation
RUN time monitor

D016

RUN

0000000hr

Displays total time the inverter has
been in RUN mode in hours.
Range is 0 to 9999 / 1000 to 9999 /
ª100 to ª999 (10,000 to 99,900)



hours

Cumulative power-on time
monitor

D017

RUN

0000000hr

Displays total time the inverter has
been powered up in hours.
Range is 0 to 9999 / 1000 to 9999 /
ª100 to ª999 (10,000 to 99,900)



hours

Cooling Fin temperature
monitor

D018

TH-Fin

0000.0 C

Temperature of the cooling fin.
(0.0~200)



qC

Trip Event and History Monitoring

The trip event and history monitoring feature lets you cycle through related information
using the keypad. See “

Monitoring Trip Events, History, & Conditions

” on page 6-5 for

more details.

“D” Function

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

Units

Trip counter

D080

ERR CNT

00000

Number of trip events,
Range is 0. to 9999



events

Trip monitor 1

D081

ERR1

########



Trip monitor 2

D082

ERR2

########





Trip monitor 3

D083

ERR3

########

Displays trip event information:
x Error code
x Output frequency at trip point
x Motor current at trip point
x DC bus voltage at trip point
x Cumulative inverter operation

time at trip point

x Cumulative power-ON time at

trip point





DC bus voltage monitor

D102

Vpn

0000.0Vdc

Voltage of inverter internal DC bus,
Range is 0.0 to 999.9



V

Electronic thermal monitor

D104

E-THM

0000.0%

Accumulated value of electronic
thermal detection, range is from 0.0
to 100.0



%

3

7

Config

uri
ng Driv

e

Parameters

3

−7

&RQ¿JXULQJ'ULYH

Parameters

Advertising