B−10, B 10, Explanation of function codes – XLT Hitachi X200 User Manual

Page 253

Advertising
background image

Explanation of function codes

Read Coil Status [01h]:

This function reads the status (ON/OFF) of selected coils. An example follows below.

x Read intelligent input terminals [1] to [5] of an inverter having a slave address “8.”

x This example assumes the intelligent input terminals have terminal states listed

below.

Item

Data

Intelligent input

terminal

[1]

[2]

[3]

[4]

[5]

Coil number

7

8

9

10

11

Coil Status

ON

OFF

ON

OFF

OFF

Query:

Response:

No.

Field Name

Example

(Hex)

No.

Field Name

Example

(Hex)

1

Slave address *1

08

1

Slave address

08

2

Function code

01

2

Function code

01

3

Coil start address *4
(high order)

00

3

Data size (in bytes)

01

4

Coil start address *4
(low order)

06

4

Coil data *3

05

5

Number of coils
(high order *2)

00

5

CRC-16 (high order)

92

6

Number of coils
(low order *2)

05

6

CRC-16 (low order)

17

7

CRC-16 (high order)

1C

8

CRC-16 (low order)

91

Note 1:

Broadcasting is disabled.

Note 2:

When 0 or more than 31 is specified as a number of coils, error code “03h” is
returned.

Note 3:

Data is transferred by the specified number of data bytes (data size).

Note 4:

The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31
are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1
less than the Coil Number.

x The data set in the response shows terminal state of coils 7 to 14.

x Data “05h = 00000101b” indicates the following assuming coil 7 is the LSB.

Item

Data

Coil Number

14

13

12

11

10

9

8

7

Coil Status

OFF

OFF

OFF

OFF

OFF

ON

OFF

ON

x When a read coil is outside the defined coils, the final coil data to be transmitted

contains “0“as the status of the coil outside the range.

x When the Read Coil Status command cannot be executed normally, see the exception

response.

B

10

Appe

ndix B

B

−10

Appendix B