Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 41

Advertising
background image

ST3000 Series Hardware Manual

3-10

‹ Serial Interface (COM2)

This interface is used to connect an RS-485 (MPI only) serial cable. A D-Sub 9-pin socket connector is used.

<ST unit side>

<Cable side>

ST Connector

XM3B-0942-502LX <OMRON Co.>

Interfit Bracket

#4-40 inch screws are used.

Recommended Cable Connector

XM2A-0901 <OMRON Co.>

Recommended Cable Cover

XM2S-0913 <OMRON Co.>

Recommended Jack Screw

XM2Z-0073 <OMRON Co.>

Pin

Arrangement

Pin No.

RS-485 (MPI only)

Signal Name

Direction

Meaning

1

NC

-

-

2

NC

-

-

3

LINE(+)

Input/

Output

LINE(+)

4

RS(RTS)

Output

Request to Send

5

SG

-

Signal Ground

*1

*1.

The SG and FG terminals are isolated.

6

5V

-

5V External Output

*2

*3

*2.

The 5V output for Pin # 6 is not protected against overcurrent. To prevent damage or

unit malfunctions, use only the rated current.

*3.

When providing power via the Siemens Co.’s PROFIBUS connector, power cannot

be connected to the Device/PLC.

7

NC

-

-

8

LINE(-)

Input/

Output

LINE(-)

9

NC

-

-

Shell

FG

-

Frame Ground

*1

(Common with SG)

9

6

5

1

(ST unit side)