Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 89

Advertising
background image

ST3000 Series Hardware Manual

4-10

‹ Wiring

When connecting the Power Cord, use the following items when performing wiring. (Items are made by

Phoenix Contact.)

‹ Connecting the Power Cord

When using the ST-3200/3300/3400 Series

(1)

Confirm that the power cord is unplugged from the power supply.

(2)

Remove the power connector (plug) from the main unit when using the ST-3200/3300 Series.

(When using ST-3400 Series, the power connector (plug) is packaged with other accessories.)

(3)

Strip the sheath of the power cord, twist the wire ends, and connect them to the Power Connector.

(4)

Reattach the Power Connector.

Recommended Driver

SZF 1-0.6x3.5 (1204517)

Recommended Pin
Terminals

AI 0.75-8GY (3200519)
AI 1-8RD (3200030)
AI 1.5-8BK (3200043)
AI 2.5-8BU (3200522)

Recommended Pin
Terminal Crimp Tool

CRIMPFOX ZA3 (1201882)

• Be sure to remove the connector from the ST unit prior to starting wiring. Failure

to do so may cause an electric shock.

• The temperature rating of field installed conductors: 75°C only.

• Use a slot screwdriver (Size 0.6 X 3.5) to tighten the terminal screws.

The torque required to tighten these screws is 0.5 to 0.6N

•m [5-7Lb•In.].

• Do not solder the cable connection.

Be sure to twist the power cords together, up to the power connector.