Chapter 3 Specifications

3-31

3.3.3

Interface Specifications

This section describes the specifications of each interface of the ST Series unit.

„ Serial Interfaces

‹ Serial Interface (COM1)

This interface is used to connect an RS-232C serial cable. A D-Sub 9-pin plug connector is used.

<ST unit side>

<Cable side>

• The ST unit’s serial port is not isolated. When the host (PLC) unit is also not

isolated, be sure to connect Pin #5 SG (Signal Ground) terminal to reduce the

risk of damaging the RS-232C/RS-422/RS-485 circuit.

• When connecting an external device to the ST using the SG terminal, be sure to

check that no short-circuit loop is created when you setup the system.

• The same type of connector is used for COM1 and COM2 of the ST. Be careful

not to mistake one for the other. Connecting them incorrectly disables

communication.

Connecting the RS-232C isolation unit (CA3-ISO232-01) to COM1 enables isolation if

needed.

ST Connector

XM2C-0942-502LX <OMRON Co.>

Interfit Bracket

#4-40 inch screws are used.

Recommended Cable Connector

XM2D-0901 <OMRON Co.>

Recommended Cable Cover

XM2S-0913 <OMRON Co.>

Recommended Jack Screw

XM2Z-0073 <OMRON Co.>

Pin

Arrangement

Pin No.

RS-232C

Signal Name

Direction

Meaning

1

CD

Input

Carrier Detect

2

RD(RXD)

Input

Receive Data

3

SD(TXD)

Output

Send Data

4

ER(DTR)

Output

Data Terminal Ready

5

SG

-

Signal Ground

6

DR(DSR)

Input

Data Set Ready

7

RS(RTS)

Output

Request to Send

8

CS(CTS)

Input

Send Possible

9

CI(RI)/VCC

Input/-

Called status display

+5V

±

5% Output 0.25A

*1

*1.

The RI/VCC selection for Pin #9 is switched via software. The VCC output is not

protected against overcurrent. To prevent damage or a unit malfunction, use

only the rated current.

Shell

FG

-

Frame Ground

(Common with SG)