3 interface specifications, 3 interface specifications -19 – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 50

Advertising
background image

Chapter 3 Specifications

3-19

3.2.3

Interface Specifications

This section describes the specifications of each interface of the ST Series unit.

„ AST-3301B, AST-3301S, AST-3301T

‹ Serial Interface (COM1)

This interface is used to connect an RS-232C serial cable. A D-Sub 9-pin plug connector is used.

<ST unit side>

<Cable side>

*1

The RI/VCC selection for Pin #9 is switched via software. The VCC output is not protected against

overcurrent. To prevent damage or a unit malfunction, use only the rated current.

• The serial interface of the ST Series (except AST-3302B COM2) does not have

an isolation function. When the host (PLC) unit is also not isolated, be sure to

connect Pin #5 SG (Signal Ground) terminal to reduce the risk of damaging the

RS-232C/RS-422/RS-485 circuit.

• ST Series (except AST-3302B COM2) have the SG (signal ground) connection

and the FG (frame ground) connection inside. When connecting an external

device to the ST using the SG terminal, be sure to check that no short-circuit loop

is created when you setup the system.

• The same type of connector is used for COM1 and COM2 of the ST (except AST-

3302B). Be careful not to mistake one for the other. Connecting them incorrectly

disables communication.

Connecting the RS-232C isolation unit (CA3-ISO232-01) to COM1 enables isolation if

needed.

ST Connector

XM2C-0942-502LX <OMRON Co.>

Interfit Bracket

#4-40 inch screws are used.

Recommended Cable Connector

XM2D-0901 <OMRON Co.>

Recommended Cable Cover

XM2S-0913 <OMRON Co.>

Recommended Jack Screw

XM2Z-0073 <OMRON Co.>

Pin

Arrangement

Pin No.

RS-232C

Signal Name

Direction

Meaning

1

CD

Input

Carrier Detect

2

RD(RXD)

Input

Receive Data

3

SD(TXD)

Output

Send Data

4

ER(DTR)

Output

Data Terminal Ready

5

SG

-

Signal Ground

6

DR(DSR)

Input

Data Set Ready

7

RS(RTS)

Output

Request to Send

8

CS(CTS)

Input

Send Possible

9

CI(RI)/VCC

Input/-

Called status display

+5V

±

5% Output 0.25A

*1

Shell

FG

-

Frame Ground

(Common with SG)

9

6

5

1

(ST unit side)