Chapter 4 Installation and Wiring

4-13

4.2.3

Grounding

This section describes the precautions for grounding the ST unit.

• When supplying power to the ST unit, be sure to separate the

input/output and power lines, as shown. [diagram (a)]

• If exclusive grounding is not possible, use a common

grounding point. [diagram (b)] A D-type grounding or

equivalent should be used for the grounding point.

4.2.4

I/O Signal Line Placement

Input and output signal lines must be separated from the power control cables for operating circuits.

If this is not possible, use a shielded cable and connect the shield to the ST unit’s frame.

Do not use common grounding, since it can lead to an accident or machine breakdown.

• Check that the grounding resistance is

100

Ω or less.

• FG and SG terminals are internally

connected in the ST. When connecting

an external device to the ST using the

SG terminal, be sure to check that no

short-circuit loop is created when you

setup the system.

• The grounding wire should have a

cross sectional area greater than

2mm

2

. Create the grounding point as

close to the ST unit as possible, and

make the wire as short as possible.

When using a long grounding wire,

replace the thin wire with a thicker wire,

and place it in a duct.

If the equipment does not function properly

when grounded, disconnect the ground wire

from the FG terminal.

(a) Exclusive Grounding (BEST)

(b) Exclusive Grounding (OK)

(C) Common Grounding (Not OK)

ST

ST

Other

Equipment

ST

Other

Equipment

Other

Equipment