1-4

IM WX101-01E

• Data Monitor

Data Monitor is started from Software Manager.

This application can display the data that have been scanned by the Logging Software
and the alarm conditions on the following five types of monitor screens. Each monitor
displays tags that have been assigned to the recorder’s channels using Tag Editor by

groups that have been assigned using Group Editor.

In addition, the display setting dialog box of Data Monitor can be used to change the

tag assignments, ON/OFF setting for each tag, specify the meters to be used on the

meter monitor, set the tag display color, and set other display conditions.

The display is updated at the scan interval.

• Trend monitor

Displays the waveform of the scanned data for each group. You can change the

display conditions such as zooming in or out of the time axis and specifying the

Y-axis zone to be displayed.

• Numeric monitor

Displays the numerical values of the scanned data for each group.

• Meter monitor

Displays the meters of the scanned data for each group. You can select the type of

meter from bar meter, analog meter, and thermometer.

• Alarm monitor

Lists the representative alarm status for each group on a single screen (alarm

overview display). If an alarm is occurring on any one of the tags in a group, the

representative alarm status is shown as “Alarm ON.”

It also displays a log of alarm occurrences/releases for each tag including the alarm

type, date and time of occurrence/release, and tag name (alarm log display).

• Color graph monitor

Displays the scanned data on a color graph for each group. The scanned data are

colored in the following order: blue (minimum value), light blue, green, yellow, and

red (maximum value).

For the operation procedure of Data Monitor, see chapter 3.

• Historical Viewer

Viewer is started from Software Manager or the Windows Start menu.

Viewer is used to manage the data that have been recorded and stored by the

Logging Software to the hard disk or a storage medium. For data that are currently

being recorded, Viewer can manage the section that have been stored to the hard

disk.

• Displays the waveforms and numerical values of data of up to 32 tags per group for

up to 50 groups.

• You can change the original data-to-tag assignments, turn ON/OFF the tags,

and change other display conditions. You can also save the modified display
conditions.

• Calculates the maximum, minimum, P-P, average, and rms values over the area

that is specified by the cursor.

• You can set conditions and search for the measured/computed data, alarms, and

marks.

• You can extract a section of the file to be stored to another file.

1.1 Overview of the DAQLOGGER/DAQLOGGER Client Package