Index – Yokogawa DAQWORX User Manual

Page 65

Advertising
background image

2-45

IM WX101-01E

1

2

3

4

5

6

7

8

9

Index

Configuring the DAQLOGGER

Sum and accumulating total
• Sum

This value is computed by summing the data over an hour for hourly reports, over a

day for daily reports, over a week for weekly reports, and over a month for monthly

reports. It is reset at the time when the corresponding report is generated.

• Accumulating total

Accumulating total can be specified only on hourly and daily reports.

For hourly reports, this value is computed by summing the data until the time the

report is generated (the report creation time set for daily reports). It is reset every day

at the report creation time set for daily reports (the value is the same as the sum of the

daily report).

For daily reports, this value is computed by summing the data until the date and time

the report is generated (the report creation date and time set for monthly reports). It

is reset every month at the report creation date and time set for monthly reports (the

value is the same as the sum of the monthly report).

The following example shows the accumulating total for hourly reports. The time

when the daily report is generated is 8 O’clock.

7:00 8:00 9:00 10:00

Time

Hourly report creation
Specified time for creating the report

Computation result

Accumulating total

Sum

8:00 9:00 10:00 11:00

About the sum unit

In the sum computation, data are summed over the scan interval. However, for flow

values that have units /s, /min, /h, or /day a simple summation results in the actual value

not matching the computed result, because the scan interval and the unit of the input

values are different. In these cases, the unit of the data measured over the scan interval

is converted to match the unit of the input values and the computation is performed.

For example, if the scan interval is 2 s, and the input value is 100 m

3

/min, a simple

summation would add 100 every 2 s resulting in 3000 after one minute. However, if the

sum unit is set to /min, then 2s/60s is multiplied every scan interval before the value is

added giving a result that is close to the actual input value. The scan interval unit is in

seconds.

Sum Unit

Conversion

Off

∑(measured/computed value)

/s

∑(measured/computed value) × data acquiring interval*

/min

∑(measured/computed value) × data acquiring interval*/60

/h

∑(measured/computed value) × data acquiring interval*/3600

/day

∑(measured/computed value) × data acquiring interval*/86400

*

Data acquiring interval refers to scan interval or record interval.

2.10 Configuring the Report Function