IM WX101-01E

• Scale over

Settings

Description

Free

The value is set to –over range if the value is less than –30000 and +over
range if the value is greater than 30000 excluding the decimal point. The value
is displayed as –Over and +Over, respectively.

Over

The value is set to –over range if the value is less than –5% of the scale and
+over range if the value is greater than 105%. The value is displayed as –Over
and +Over, respectively.

Example:

If the scale is 0.0 to 200.0, the value is set to –over range if the value is less than

–10.0 of the scale and +over range if the value is greater than 210.0.

Note

For computations such as TLOG, CLOG, and report, the handling of the scale over-range value

can be set in advance.

• Key Security

Settings

Description

Login

Enables only registered users to operate the DX using keys. The [User
registration] is displayed in the [Basic Setting] tab. The Key Security setting is
fixed at [Login] on DXs with the /AS1 advanced security option.

Keylock

Enables the key lock function. Set the key lock function in the [Basic Setting] tab.
This option cannot be selected on DXs with the /AS1 advanced security option.

OFF

Disables the security functions. This option cannot be selected on DXs with the
/AS1 advanced security option.

• Comm. Security

Settings

Description

Login

Enables only registered users to operate the DX via communications. The [User
registration] is displayed in the basic setting mode menu.

OFF

Disables the security functions.

• Multi Login (Only on DXs with the /AS1 advanced security option)

Setting

Description

On

The multi-login function is used. At the same time, one user can log in through
key operations, one through an Ethernet connection (connection to the setting
function), and one through serial communication.

Off

The multi-login function is not used. Users cannot log in simultaneously
through key operations, Ethernet (connection to the setting function), or serial
communication (LL command).

• Password Management (Only on DXs with the /AS1 advanced security

option)

To perform password management using a KDC server on the Ethernet, select [On].

You will have to set the [Ethernet communication] - [Password management] item.

• Auto Save

Settings

Description

ON

Automatically saves the measured data to the CF card.

OFF

Does not automatically save the data. Save the measured data manually to
the CF card or USB flash memory (/USB1 option).

• Media FIFO

You can select this with DX main unit firmware version 2.0x or later.

This is valid only when [Auto Save] is [ON].

Settings

Description

ON

If there is no more free space on the CF card, the oldest file is deleted, and
the newest file is saved.

OFF

If there is no more free space on the CF card, the measured data is not saved
to the CF card.

7.7 Setting DX1000/DX2000