9-2

IM WX101-01E

Logger Software

Error

Code

Error message

What to do

E3001

Failed to open data file.

Check if the disk capacity is sufficient or if the file system is
normal.

E3002

Failed to write data file.

Check if the disk capacity is sufficient or if the file system is
normal.

E3003

Failed to open alarm log.

Check if the disk capacity is sufficient, if you are using programs
other than DAQLOGGER, or if the file system is normal.

E3004

Failed to write alarm log.

Check if the disk capacity is sufficient, if the alarm log file is
being used by another application, or if the file system is normal.

E3005

Tag is not specified. Please specify tag first.

Specify the tag to collect data with the Tag Editor.

E3006

Connection failure for all devices.

Use the Software Configurator to check the settings for
communication with recorders. Also refer to the instructions for
E0401, because the error may be a communication error.

E3007

No available monitor server exists or No monitor
server which is logging data exists.

Check the settings for communication with the monitor
server on the Software Configurator. Confirm that the monitor
server starts, and whether or not data is being logged.

E3008

No available device exists.No available monitor
server

exists or No monitor server which is logging data
exists.

Check the settings for communication with the recorder or

monitor server on the Software Configurator.

Communication errors can occur with recorders. Therefore,
refer also to E0401.

In the case of monitor servers, confirm that the monitor server
starts, and check whether or not data is being logged.

Warning

Code

Warning message

What to do

W3030

Connection failure for some devices.

Use the Software Configurator to check the settings for
communication with recorders. Also refer to the instructions for
E0401, because the error may be a communication error.

W3031

Some unconnected monitor server exists or Some
monitor server is not logging data.

Check the settings for communication with the monitor

server on the Software Configurator. Confirm that the monitor
server starts, and whether or not data is being logged.

W3032

Some unconnected devices exists. Some
unconnected

monitor server exists or Some monitor server is not
logging data.

Check the settings for communication with the recorder or

monitor server on the Software Configurator.

Communication errors can occur with recorders. Therefore,
refer also to E0401.

In the case of monitor servers, confirm that the monitor server
starts, and check whether or not data is being logged.

Viewer

Error

Code

Message

What to do

M3101

There are no data.

— — — —

M3102

There are no saved tags.

— — — —

Tag Editor

Error

Code

Warning message

What to do

W3201

No recorder is assigned to this tag number.
Please assign a recorder to the tag number.

Assign a recorder to the tag number.

W3202

Settings don’t fit currently connected model.

Use the Software Configurator to check the connected recorder.

W3407

Communication settings are incomplete.

Use the Software Configurator to check the communication
settings.

Message

Code

Message

What to do

M3204

There are characters that can not be displayed in the
data.

They are replaced by spaces.

— — — —

M3205

Maximum number of characters exceeded.
Tags were aquired with only the first 16 characters.

— — — —

9.1 Error Messages and Their Corrective Actions