Installation, 2 electrical installation, 1 power connections – Sterling RT User Manual

Page 15: 1 mains connection to 120vac single-phase supply, 2 mains connection to 240vac single-phase supply

Advertising
background image

14

SV01H

Installation

3.2

Electrical Installation

3.2.1

Power Connections

DANGER! Hazard of electrical shock!
Circuit potentials up to 600 VAC are possible. Capacitors retain charge after power is
removed. Disconnect power and wait at least three minutes before servicing the drive.

STOP!

• Verify mains voltage before connecting to drive.
• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the drive will result.
• Do not cycle mains power more than once every two minutes. Damage to the drive will result.

Mains and Motor Terminations

Type

Torque

Strip Length

<5HP

12 lb-in (1.3 Nm)

0.25 in (6mm)

ESV552xx2T, ESV752xx2T, ESV113xx4/6, ESV153xx4/6, ESV183xx6, ESV223xx6

16 lb-in (1.8 Nm)

0.25 in (6mm)

ESV552xx4Txx, ESV752xx4Txx, ESV552xx6Txx, ESV752xx6Txx

12 lb-in (1.3Nm)

0.25 in (6mm)

ESV113xx2xxx, ESV153xx2xxx, ESV183xx4xxx, ESV223xx4xxx

24 lb-in (2.7 Nm)

0.25 in (6mm)

Torque: N4X/IP65 Door Screws

N4X/IP65

6-7 lb-in (0.67-0.79 Nm)

0.25 in (6mm)

3.2.1.1

Mains Connection to 120VAC Single-Phase Supply

ESV...N01S...

PE L1 L2 N

PE L1

N

3.2.1.2

Mains Connection to 240VAC Single-Phase Supply

ESV...N01S...

PE L1 L2 N

PE L1 L2

ESV...N01S...

PE L1 L2 N

PE L1 N

ESV...N02Y...
(2/PE AC)

PE L1 L2 L3

PE L1 L2

ESV...N02Y...
(1/N/PE AC)

PE L1 L2 L3

PE L1 N

ESV...N02S...
(2/PE AC)

PE L1 L2

PE L1 L2

ESV...N02S...
(1/N/PE AC)

PE L1 L2

PE L1 N