Commissioning, 7 diagnostic parameters – Sterling RT User Manual

Page 39

Advertising
background image

38

SV01H

Commissioning

4.5.7

Diagnostic Parameters

Code

Display Range

(READ ONLY)

IMPORTANT

No.

Name

p 0

Fault History

• Displays the last 8 faults
• Format: n.xxx

where: n = 1..8;

1 is the newest fault

xxx = fault message (without the

.)

• Refer to section 5.3

P 1

Software Version

Format: x.yz

P 2

Drive ID

A flashing display indicates that the Drive ID stored in the
EPM does not match the drive model it is plugged into.

P

Internal Code

Alternating Display: xxx-; -yy

P

DC Bus Voltage

0

{VDC}

1500

P

Motor Voltage

0

{VAC}

1000

P 7

Load

0

{%}

255

Motor load as % of drive’s output current rating.
Refer to section 2.3.

P

Motor Current

0.0

{A}

1000

Actual motor current

P

Torque

0

{%}

500

Torque as % of motor rated torque
(vector mode only)

0

kW

0.00

{kW}

650.0

P 1

kWh

0.0

{kWh}

9999999 Alternating display: xxx-; yyyy when value exceeds 9999

P 2

Heatsink Temp

0

{°C}

150

Heatsink temperature

P 0

0-10 VDC Input

0.0

{VDC}

10.0

Actual value of signal at TB-5

P 1

4-20 mA Input

0.0

{mA}

20.0

Actual value of signal at TB-25

P 2

TB-5 Feedback

P204

P205

TB-5 signal value scaled to PID feedback units

P

TB-25 Feedback

P204

P205

TB-25 signal value scaled to PID feedback units

Analog Output

0

{VDC}

10.0

Refer to P150…P155

7

Actual Output
Frequency

0

{Hz}

500.0

P 8

Network Speed
Command

0

{Hz}

500.0

Command speed if (Auto: Network) is selected as the
speed source

P 0

Terminal and
Protection Status

Indicates terminal status using segments of the LED
display. (Refer to section 4.5.7.1)

1

Keypad Status

Indicates keypad button status using segments of the
LED display. (Refer to section 4.5.7.2)

P 0

Total Run Time

0

{h}

9999999 Alternating display: xxx-; yyyy when value exceeds 9999

P 1

Total Power On Time 0

{h}

9999999