Commissioning – Sterling RT User Manual

Page 33

Advertising
background image

32

SV01H

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

17

(1)

Current Limit

Max I

30

{%}

Max I

• When the limit is reached, the drive

displays (Current Limit), and either the
acceleration time increases or the output
frequency decreases.

• Digital outputs can also indicate when the

limit is reached; see P140, P142.

• Refer to section 2.3 for the maximum output

current

Max I (%)

DC Brake Voltage

0.0

0.0

{%}

30.0

Setting is a percent of the nominal DC bus
voltage.

p

DC Brake Time

0.0

0.0

{s}

999.9

NOTE
CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING

DC Brake voltage (P174) is applied for the time specified by P175 with the following
exceptions:
• If P111=1, 3 and P175=999.9 the brake voltage will be applied continuously until a

run or fault condition occurs.

• If P110=2, 4…6 and P175=999.9, brake voltage will be applied for 15s
• If P121…P124=18 and the corresponding TB-13 input is CLOSED, brake voltage will

be applied until the TB-13 input is OPENED or a fault condition occurs.

p 7

Speed Units

0

0 Hz

Select the UNITS LED that will be illuminated
when the drive is running in speed control
mode. For this parameter to be used, P178
must be set to a value other than 0. IF P178
is set to 0, the HZ LED will be illuminated
regardless of the value set in P177.

1 RPM
2 %
3 /UNITS
4 NONE
NOTE:
P177 is applicable to SMV 15HP (11kW) and greater models only.

Display Frequency
Multiplier

0.00

0.00

650.00

• Allows frequency display to be scaled
• P178 = 0.00: Scaling disabled
• P178 > 0.00: Display = Actual Frequency X

P178

EXAMPLE
If P178 = 29.17 and actual frequency = 60 Hz, then Drive displays 1750 (rpm)

p

Run Screen Display

0

0 {Parameter Number}

599

• 0 = Normal Run Screen, this display

depends on mode of operation.
Refer to section 4.2.

• Other selections choose a diagnostic

parameter to display (P501…P599).

(1) Any changes to this parameter will not take effect until the drive is stopped

Advertising
This manual is related to the following products:

PV, MS, ME, AH