Commissioning

4.5.2

I/O Setup Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p 0

Assertion Level

2

1 Low

P120 and the Assertion Level switch must both
match the desired assertion level unless P100,
P121…P124 are all set to 0. Otherwise an
F.AL fault will occur.

2 High

1

p 2

p

p 4

TB-13A Input
Function

TB-13B Input
Function

TB-13C Input
Function

TB-13D* Input
Function

0

0 None

Disables input

1 AUTO Reference: 0-10 VDC

For frequency mode, see P160...P161,
For PID mode, see P204…P205,
For vector torque mode, see P330

2 AUTO Reference: 4-20 mA

3 AUTO Reference: Preset

* 13D: 3 = Reserved

For frequency mode see P131...P137,
For PID mode, see P231…P233,
For torque mode see, P331…P333

4 AUTO Reference: MOP Up

• Normally open: Close input to increase or

decrease speed, PID or torque setpoint.

• MOP Up is not active while in STOP

5 AUTO Reference: MOP Down

6 AUTO Reference: Keypad

7 AUTO Reference: Network
8 Control Select

Use when P100 = 4, 5 to switch between
terminal strip control and local or remote
keypad control.

9 Network Enable

Required to start the drive through the
network.

10 Reverse Rotation

Open = Forward Closed = Reverse

11 Start Forward

Refer to Note for typical circuit

12 Start Reverse
13 Run Forward

Refer to Note for typical circuit

14 Run Reverse
15 Jog Forward

Jog Forward speed = P134

16 Jog Reverse

Jog Reverse speed = P135

Active even if P112 = 0

17 Accel/Decel #2

Refer to P125, P126

18 DC Brake

Refer to P174; close input to override P175

19 Auxiliary Ramp to Stop

Normally closed: Opening input will ramp drive
to STOP according to P127, even if P111 is set
to Coast (0 or 1).

20 Clear Fault

Close to reset fault

21 External Fault .

Normally closed circuit; open to trip

22 Inverse External Fault .

Normally open circuit; close to trip

WARNING!
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be deactivated or a fault
condition induced.

NOTE: P124 is
applicable to SMV
15HP (11kW) and
greater models only