Commissioning – Sterling RT User Manual

Page 36

Advertising
background image

35

SV01H

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p 0

PID Setpoint Ramp

20.0

0.0

{s}

100.0

• time of setpoint change from P204 to P205

or vice versa.

• Used to smooth the transition from one PID

setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)

p

Minimum Alarm

0.0

P204

P205

Use with P140, P142 = 18...23

P

Maximum Alarm

0.0

P204

P205

P 1

Preset PID Setpoint
#1

0.0

P204

P205

TB-13A activated; P121 = 3 and
P200 = 1 or 2

P 2

Preset PID Setpoint
#2

0.0

P204

P205

TB-13B activated; P122 = 3 and
P200 = 1 or 2

Preset PID Setpoint
#3

0.0

P204

P205

TB-13C activated; P123 = 3 and
P200 = 1 or 2

P 0

Sleep Threshold

0.0

0.0

{Hz}

500.0

• If drive speed < P240 for longer than P241,

output frequency = 0.0 Hz; drive display =

• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again when

speed command is above P240

• P242 > 0.0: Drive will restart when the PID

feedback differs from the setpoint by more
than the value of P242

or when the PID

loop requires a speed above P240.

P 1

Sleep Delay

30.0

0.0

{s}

300.0

P 2

Sleep Bandwidth

0.0

0.0

B

max

Where: B

max

= |(P205 - P204)|