Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P 1

Network Baud Rate

0 2400 bps

Modbus

1 4800 bps
2 9600 bps
3 19200 bps

0

0 9600 bps

Lecom

1 4800 bps
2 2400 bps
3 1200 bps
4 19200 bps

P 2

Network Data Format

0 8, N, 2

Modbus Only

1 8, N, 1
2 8, E, 1
3 8, O, 1

Network Control
Level

0

0 Monitor Only

Lecom Only

1 Parameter Programming
2 Programming and Setpoint Control
3 Full Control

P

Network Powerup
Start Status

0

0 Quick Stop

Lecom Only

1 Controller Inhibit

p

Network Timeout

0

0.0 - 300.0 seconds

Modbus

0 - 65000 milliseconds

Lecom

P

Network Timeout
Action

4

0 No action

Modbus

1 Stop (P111)
2 Quick Stop
3 Controller Inhibit
4 Trip Fault, F.nF1

0

0 No action

Lecom

1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1

P 7

Network Messages
Received

Read-Only: 0 - 9999

Valid network messages received

NOTE: When the number of messages exceeds 9999, the counter resets and resumes
counting from 0.