Safety information, Safety information in accordance with ul – Sterling RT User Manual

Page 6

Advertising
background image

5

SV01H

Safety Information

Harmonics Notification in accordance with EN 61000-3-2, EN 61000-3-12:

Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic Compatibility
(EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/phase).

Directive

Total Power

connected to Mains

(public supply)

Additional Measures Required for Compliance

(2)

EN 61000-3-2

< 0.5kW

with mains choke

0.5 ... 1kW

with active filter

> 1kW

complies without additional measures

EN 61000-3-12

16 ... 75amp

Additional measures are required for compliance with the standard

(1) For compliance with EMC regulations, the permissable cable lengths may change.
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.

The machine/system manufacturer is responsible for the machine’s compliance with the regulations.

Safety Information in accordance with EN 61800-5-1:

DANGER! Hazard of Electrical Shock

Capacitors retain charge for approximately 180 seconds after power is removed. Allow
at least 3 minutes for discharge of residual charge before touching the drive.

WARNING!

• This product can cause a d.c. current in the PE conductor. Where a residual current-operated

(RCD) or monitoring (RCM) device is used for protection in case of direct or indirect contact, only
an RCD or RCM Type B is allowed on the supply side of this product.

• Leakage Current may exceed 3.5mA AC. The minimum size of the PE conductor shall comply with

local safety regulations for high leakage current equipment.

• In a domestic environment, this product may cause radio interference in which case

supplementary mitigation measures may be required.

NOTE

Control and communications terminals provide reinforced insulation when the drive is connected to a
power system rated up to 300V rms between phase to ground (PE) and the applied voltage on Terminals
16 and 17 is less than 150VAC between phase and ground.
Control and communications terminals provide basic insulation when the drive is connected to a power
system rated up to 300V between phase to ground (PE) and the applied voltage on terminals 16 and 17
is less than 250 VAC between phase phase and ground (PE).

Safety Information in accordance with UL:

Note for UL approved system with integrated controllers: UL warnings are notes which apply to UL systems. The
documentation contains special information about UL.

Warnings!

• Suitable for use on a circuit capable of delivering not more than 200,000 rms symmetrical

amperes, at the maximum voltage rating marked on the drive.

• Use minimum 75 °C copper wire only.
• Shall be installed in a pollution degree 2 macro-environment.
• NEMA 1 (IP31) models shall be installed in a pollution degree 2 macro-environment.
• All models are suitable for installation in a compartment handling Conditioned Air.

Torque Requirements (in accordance with UL) are listed in section 3.2.1, Power Connections.