Commissioning, 5 vector parameters – Sterling RT User Manual

Page 37

Advertising
background image

36

SV01H

Commissioning

4.5.5

Vector Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

(1)

Drive Mode

0

0 Constant V/Hz

Constant torque V/Hz control for general
applications

1 Variable V/Hz

Variable torque V/Hz control for centrifugal
pump and fan applications

2 Enhanced Constant V/Hz

For single or multiple motor applications that
require better performance than settings 0 or
1, but cannot use Vector mode, due to:
• Missing required motor data
• Vector mode causing unstable motor

operation

3 Enhanced Variable V/Hz

4 Vector Speed

For single-motor applications requiring higher
starting torque and speed regulation

5 Vector Torque

For single-motor applications requiring torque
control independent of speed

NOTE
To configure the drive for either Vector mode or Enhanced V/Hz mode:
• P300 = 4, 5:

- Set P302...P306 according to motor nameplate

- Set P399 = 1

- Make sure motor is cold (20° - 25° C) and apply a Start command

- Display will indicate

for about 40 seconds

- Once the calibration is complete, the display will indicate

; apply another

Start command to actually start the motor

- If an attempt is made to start the drive in Vector or Enhanced V/Hz mode before

performing the Motor Calibration, the drive will display

and will not

operate

• P300 = 2, 3: Same as above but only need to set P302…P304

(1)

Motor Rated Voltage

0

{V}

600

• Default setting = drive rating
• Set to motor nameplate data

(1)

Motor Rated Current

0.0

{A}

500.0

(1)

Motor Rated
Frequency

60

0

{Hz}

1000

Set to motor nameplate data

(1)

Motor Rated Speed

1750

300

{RPM}

65000

P 6

(1)

Motor Cosine Phi

0.80

0.40

0.99

NOTE
If motor cosine phi is not known, use one of the following formulas:
cos phi = motor Watts / (motor efficiency X P302 X P303 X 1.732)
cos phi = cos [ sin

1

(magnetizing current / motor current) ]

(1)

Motor Stator
Resistance

0.00

0.00

{

Ω}

64.00

• Will be automatically programmed by P399
• Changing these settings can adversely

affect performance. Contact factory
technical support prior to changing

(1)

Motor Stator
Inductance

0.0

0.0

{mH}

2000

P 0

Torque Limit

100

0

{%}

400

When P300 = 5, sets the maximum output
torque.

(1) Any changes to this parameter will not take effect until the drive is stopped