Troubleshooting and diagnostics, 3 fault messages – Sterling RT User Manual

Page 44

Advertising
background image

43

SV01H

Troubleshooting and Diagnostics

5.3

Fault Messages

The messages below show how they will appear on the display when the drive trips. When looking at the Fault History
(P500), the

_ will not appear in the fault message.

Fault

Cause

Remedy

(1)

.

High Temperature fault

Drive is too hot inside

• Reduce drive load
• Improve cooling

L

Assertion Level fault

• Assertion Level switch is changed

during operation

• P120 is changed during operation

P100 or P121...P124 are set to a
value other than 0 and P120 does
not match the Assertion Level
Switch.

• Make sure the Assertion Level switch

and P120 are both set for the type
of input devices being used, prior to
setting P100 or P121...P124.
Refer to 3.2.3 and P120.

Personality fault

Drive Hardware

• Cycle Power
• Power down and install EPM with valid

data

• Reset the drive back to defaults (P199

= 3, 4) and then re-program

• If problem persists, contact factory

technical support

Control fault

An EPM has been installed that is either
blank or corrupted

Incompatible EPM fault

An EPM has been installed that contains
data from an incompatible parameter
version

Dynamic Braking fault

Dynamic braking resistors are overheating • Increase active decel time

(P105, P126, P127).

• Check mains voltage and P107

External fault

• P121…P124 = 21 and that digital input

has been opened.

• P121…P124 = 22 and that digital input

has been closed.

• Correct the external fault condition
• Make sure digital input is set properly

for NC or NO circuit

EPM fault

EPM missing or defective

Power down and replace EPM

Internal faults

Contact factory technical support

Control Configuration Fault

The drive is setup for REMOTE KEYPAD
control (P100=2 or 5) but is not setup to
communicate with a remote keypad

Set P400 = 1, or P600 = 1

The drive is setup for NETWORK ONLY
control (P100=3) but is not setup for
network communications

Set P400 or P600 to a valid network
communications protocol selection

L

Loss of 4-20 mA signal fault

4-20 mA signal (at TB-25) is below 2 mA
(P163 = 1)

Check signal/signal wire

.

OEM Defaults data fault

Drive is powered up with P199 =1 and
OEM settings in the EPM are not valid.

Install an EPM containing valid OEM
Defaults data or change P199 to 0.

.H

High DC Bus Voltage fault

Mains voltage is too high

Check mains voltage and P107

Decel time is too short, or too much regen
from motor

Increase active decel time
(P105, P126, P127) or install Dynamic
Braking option

(1) The drive can only be restarted if the error message has been reset.