Commissioning, 4 pid parameters – Sterling RT User Manual

Page 35

Advertising
background image

34

SV01H

Commissioning

4.5.4

PID Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P 0

PID Mode

0

0 Disabled

• Normal-acting: As feedback increases,

motor speed decreases

• Reverse-acting: As feedback increases,

motor speed increases

• PID mode is disabled in Vector Torque mode

(P300 = 5)

1 Normal-acting

2 Reverse-acting

NOTE
To activate PID mode, one of the TB-13 inputs (P121...P124) must be used to select
the Auto Reference that matches the desired PID setpoint reference. If the selected PID
setpoint reference uses the same analog signal as the PID feedback (P201), an I

fault will occur.
Example: The desired PID setpoint reference is the keypad (s and t). Set TB-13x = 6
(Auto Reference: Keypad):
• TB-13x = closed: PID mode is active
• TB-13x = open: PID mode is disabled and the drive speed will be controlled by the

reference selected in P101.

p 1

PID Feedback Source

0

0 4-20 mA (TB-25)

Must be set to match the PID feedback signal

1 0-10 VDC (TB-5)

p 2

PID Decimal Point

1

0 PID Display = XXXX

Applies to P204, P205, P214, P215, P231...
P233, P242, P522, P523

1 PID Display = XXX.X
2 PID Display = XX.XX
3 PID Display = X.XXX
4 PID Display = .XXXX

PID Units

0

0 %

Select the UNITS LED that will be illuminated
when the drive is running in PID control mode

1 /UNITS
2 AMPS
3 NONE
NOTE:
P203 is applicable to SMV 15HP (11kW) and greater models only.

p 4

Feedback at
Minimum Signal

0.0

-99.9

3100.0

Set to match the range of the feedback signal
being used
Example: Feedback signal is 0 - 300 PSI;
P204 = 0.0, P205 = 300.0

p

Feedback at
Maximum Signal

100.0 -99.9

3100.0

7

Proportional Gain

5.0

0.0

{%}

100.0

Used to tune the PID loop:
• Increase P207 until system becomes

unstable, then decrease P207 by 10-15%

• Next, increase P208 until feedback matches

setpoint

• If required, increase P209 to compensate

for sudden changes in feedback

Integral Gain

0.0

0.0

{s}

20.0

p

Derivative Gain

0.0

0.0

{s}

20.0

NOTE
• Derivative Gain is very sensitive to noise on the feedback signal and must be used

with care

• Derivative Gain is not normally required in pump and fan applications