Setting the jumpers, Nac class a or class b (jp1 and jp2), Ground fault enable (jp3) – Edwards Signaling EBPS Remote Booster Power Supply User Manual

Page 18

Advertising
background image

12

Remote Booster Power Supply Technical Reference Manual

Setting the jumpers

There are four jumpers on the BPS. See Figure 1 on page 4 for the location of
the jumpers.

NAC Class A or Class B (JP1 and JP2)

JP1 and JP2 are used to select a Class A or Class B NAC wiring configuration
for all NACs. The default is Class B.

Note:

JP1 and JP2 must be positioned to match the SW2-8 DIP switch selection

(Class A or Class B).

Figure 7: JP1 and JP2

(1)

(1)

(2)

(2)

JP1

JP2

1

1

2

2

3

3

(1) Class A
(2) Class B

Ground fault enable (JP3)

JP3 is used to set the NAC/AUX circuits for ground fault enabled or disabled
operation. The sense inputs are always isolated from local power.

Enabled:

Allows the BPS to perform its own ground fault checking. This is the

default

position.

Disabled:

Disable the BPS's ground fault detection only when the controlling

panel is providing ground fault detection for the BPS output circuits. See
Figure 8 on page 13 for wiring information.